489
GENERATOR MANAGEMENT RELAY
®
Instruction Manual
489 Firmware Revision: 32I151A8.000
489PC Software Revision: 1.5X
Manual P/N: 1601-0071-EA (GEK-106290B)
Copyright © 2006GE Multilin
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 294-8512
Internet: http://www.GEindustrial.com/multilin
Manufactured under an
ISO9001 Registered system.
g
GE Industrial Systems
808754E4.CDR
489 IN SERVICE BREAKER OPEN R1 TRIP
R2 AUXILIARY
R3 AUXILIARY
R4 AUXILIARY
R5 ALARM
R6 SERVICE
SETPOINT ACCESS
BREAKER CLOSED
COMPUTER RS232
HOT STATOR
MESSAGE
VT FAILURE
BREAKER FAILURE
489 Generator Management Relay
PROGRAM PORT
SETPOINT
7 89
4
5
6
12 3
.
0
HELP
MESSAGE
VALUE
ACTUAL
ESCAPE
ENTER
TM
RESET
NEXT
RESET
POSSIBLE
COMPUTER RS485
AUXILIARY RS485
ALT. SETPOINTS
489 STATUS GENERATOR STATUS OUTPUT RELAYS
NEG. SEQUENCE
GROUND
LOSS OF FIELD
g
SELECT CURVE STYLE:
Voltage Dependent
Zobrazit stránku 0
1 2 3 4 5 6 ... 258 259

Shrnutí obsahu

Strany 1 - Instruction Manual

REGISTERED489GENERATOR MANAGEMENT RELAY®Instruction Manual489 Firmware Revision: 32I151A8.000489PC Software Revision: 1.5XManual P/N: 1601-0071-EA (GE

Strany 2

1-2 489 Generator Management Relay GE Multilin1.1 OVERVIEW 1 INTRODUCTION1Power metering is a standard feature in the 489. The table below outlines th

Strany 3 - 4. SETPOINTS 4.1 OVERVIEW

4-50 489 Generator Management Relay GE Multilin4.9 S8 RTD TEMPERATURE 4 SETPOINTS44.9.2 RTDS 1 TO 6PATH: SETPOINTS ÖØ S8 RTD TEMPERATURE ÖØ RTD #1(6)R

Strany 4

GE Multilin 489 Generator Management Relay 4-514 SETPOINTS 4.9 S8 RTD TEMPERATURE44.9.3 RTDS 7 TO 10PATH: SETPOINTS ÖØ S8 RTD TEMPERATURE ÖØ RTD #7(10

Strany 5 - 5. ACTUAL VALUES 5.1 OVERVIEW

4-52 489 Generator Management Relay GE Multilin4.9 S8 RTD TEMPERATURE 4 SETPOINTS44.9.4 RTD 11PATH: SETPOINTS ÖØ S8 RTD TEMPERATURE ÖØ RTD #11RTD 11 d

Strany 6 - 7. TESTING 7.1 TEST SETUP

GE Multilin 489 Generator Management Relay 4-534 SETPOINTS 4.9 S8 RTD TEMPERATURE44.9.5 RTD 12PATH: SETPOINTS ÖØ S8 RTD TEMPERATURE ÖØ RTD #12RTDs 12

Strany 7

4-54 489 Generator Management Relay GE Multilin4.9 S8 RTD TEMPERATURE 4 SETPOINTS44.9.6 OPEN RTD SENSORSETPOINTS ÖØ S8 RTD TEMPERATURE ÖØ OPEN RTD SEN

Strany 8 - TABLE OF CONTENTS

GE Multilin 489 Generator Management Relay 4-554 SETPOINTS 4.10 S9 THERMAL MODEL44.10S9 THERMAL MODEL 4.10.1 489 THERMAL MODELThe thermal model of the

Strany 9 - 27TN59GN

4-56 489 Generator Management Relay GE Multilin4.10 S9 THERMAL MODEL 4 SETPOINTS44.10.2 MODEL SETUPa) DESCRIPTIONPATH: SETPOINTS ÖØ S9 THERMAL MODEL Ö

Strany 10

GE Multilin 489 Generator Management Relay 4-574 SETPOINTS 4.10 S9 THERMAL MODEL4The current measured at the output CTs is used for the thermal model.

Strany 11

4-58 489 Generator Management Relay GE Multilin4.10 S9 THERMAL MODEL 4 SETPOINTS4Figure 4–11: 489 STANDARD OVERLOAD CURVESx1x15100000100001000100101.0

Strany 12 - ≥ 2 × CT: ±1% of 20 × CT

GE Multilin 489 Generator Management Relay 4-594 SETPOINTS 4.10 S9 THERMAL MODEL4Above 8.0 × Pickup, the trip time for 8.0 is used. This prevents the

Strany 13

GE Multilin 489 Generator Management Relay 1-31 INTRODUCTION 1.1 OVERVIEW11.1.2 ORDERINGAll features of the 489 are standard, there are no options. Th

Strany 14

4-60 489 Generator Management Relay GE Multilin4.10 S9 THERMAL MODEL 4 SETPOINTS4b) CUSTOM OVERLOAD CURVEIf the induction generator starting current b

Strany 15

GE Multilin 489 Generator Management Relay 4-614 SETPOINTS 4.10 S9 THERMAL MODEL4c) VOLTAGE DEPENDENT OVERLOAD CURVEIt is possible and acceptable that

Strany 16 - LONG-TERM STORAGE

4-62 489 Generator Management Relay GE Multilin4.10 S9 THERMAL MODEL 4 SETPOINTS4To illustrate the Voltage Dependent Overload Curve feature, the therm

Strany 17

GE Multilin 489 Generator Management Relay 4-634 SETPOINTS 4.10 S9 THERMAL MODEL4The 489 takes the information provided and create protection curves f

Strany 18

4-64 489 Generator Management Relay GE Multilin4.10 S9 THERMAL MODEL 4 SETPOINTS4The following curves illustrate the resultant overload protection for

Strany 19 - 808704A1.CDR

GE Multilin 489 Generator Management Relay 4-654 SETPOINTS 4.10 S9 THERMAL MODEL4d) UNBALANCE BIASUnbalanced phase currents will cause additional roto

Strany 20

4-66 489 Generator Management Relay GE Multilin4.10 S9 THERMAL MODEL 4 SETPOINTS4e) MACHINE COOLINGThe 489 thermal capacity used value is reduced expo

Strany 21 - Figure 2–8: TERMINAL LAYOUT

GE Multilin 489 Generator Management Relay 4-674 SETPOINTS 4.10 S9 THERMAL MODEL4f) HOT/COLD CURVE RATIOWhen thermal limit information is available fo

Strany 22 - Table 2–1: 489 TERMINAL LIST

4-68 489 Generator Management Relay GE Multilin4.10 S9 THERMAL MODEL 4 SETPOINTS4It should be noted that the RTD bias feature alone cannot create a tr

Strany 23 - 2 INSTALLATION 2.2 ELECTRICAL

GE Multilin 489 Generator Management Relay 4-694 SETPOINTS 4.11 S10 MONITORING44.11S10 MONITORING 4.11.1 TRIP COUNTERPATH: SETPOINTS ÖØ S10 MONITORING

Strany 24

1-4 489 Generator Management Relay GE Multilin1.2 SPECIFICATIONS 1 INTRODUCTION11.2SPECIFICATIONS 1.2.1 489 SPECIFICATIONSPOWER SUPPLYOptions: LO / HI

Strany 25

4-70 489 Generator Management Relay GE Multilin4.11 S10 MONITORING 4 SETPOINTS44.11.3 TRIP COIL MONITORPATH: SETPOINTS ÖØ S10 MONITORING ÖØ TRIP COIL

Strany 26

GE Multilin 489 Generator Management Relay 4-714 SETPOINTS 4.11 S10 MONITORING44.11.4 VT FUSE FAILUREPATH: SETPOINTS ÖØ S10 MONITORING ÖØ VT FUSE FAIL

Strany 27

4-72 489 Generator Management Relay GE Multilin4.11 S10 MONITORING 4 SETPOINTS44.11.5 CURRENT, MW, MVAR, AND MVA DEMANDPATH: SETPOINTS ÖØ S10 MONITORI

Strany 28 - RTD SENSING

GE Multilin 489 Generator Management Relay 4-734 SETPOINTS 4.11 S10 MONITORING4The 489 can measure the demand of the generator for several parameters

Strany 29

4-74 489 Generator Management Relay GE Multilin4.11 S10 MONITORING 4 SETPOINTS44.11.6 PULSE OUTPUTPATH: SETPOINTS ÖØ S10 MONITORING ÖØ PULSE OUTPUTThe

Strany 30

GE Multilin 489 Generator Management Relay 4-754 SETPOINTS 4.12 S11 ANALOG I/O44.12S11 ANALOG I/O 4.12.1 ANALOG OUTPUTS 1 TO 4PATH: SETPOINTS ÖØ S11 A

Strany 31 - GE Multilin

4-76 489 Generator Management Relay GE Multilin4.12 S11 ANALOG I/O 4 SETPOINTS44.12.2 ANALOG INPUTS 1 TO 4PATH: SETPOINTS ÖØ S11 ANALOG I/O ÖØ ANALOG

Strany 32 - 2.2 ELECTRICAL 2 INSTALLATION

GE Multilin 489 Generator Management Relay 4-774 SETPOINTS 4.12 S11 ANALOG I/O4There are 4 analog inputs (4 to 20 mA, 0 to 20 mA, or 0 to 1 mA) that m

Strany 33 - S3 DIGITAL INPUTS /

4-78 489 Generator Management Relay GE Multilin4.13 S12 TESTING 4 SETPOINTS44.13S12 TESTING 4.13.1 SIMULATION MODEPATH: SETPOINTS ÖØ S12 TESTING Ö SIM

Strany 34 - SETPOINT

GE Multilin 489 Generator Management Relay 4-794 SETPOINTS 4.13 S12 TESTING44.13.2 PRE-FAULT SETUPPATH: SETPOINTS ÖØ S12 TESTING ÖØ PRE-FAULT SETUPThe

Strany 35 - NEW SETPOINT HAS BEEN

GE Multilin 489 Generator Management Relay 1-51 INTRODUCTION 1.2 SPECIFICATIONS1RS485 Baud Rates: 300, 1200, 2400, 4800, 9600, 19200RS232 Baud Rate: 9

Strany 36

4-80 489 Generator Management Relay GE Multilin4.13 S12 TESTING 4 SETPOINTS44.13.3 FAULT SETUPPATH: SETPOINTS ÖØ S12 TESTING ÖØ FAULT SETUPThe values

Strany 37 - 808745A1.CDR

GE Multilin 489 Generator Management Relay 4-814 SETPOINTS 4.13 S12 TESTING44.13.4 TEST OUTPUT RELAYSPATH: SETPOINTS ÖØ S12 TESTING ÖØ TEST OUTPUT REL

Strany 38

4-82 489 Generator Management Relay GE Multilin4.13 S12 TESTING 4 SETPOINTS44.13.6 COMM PORT MONITORPATH: SETPOINTS ÖØ S12 TESTING ÖØ COMM PORT MONITO

Strany 39 - 808744A1.CDR

GE Multilin 489 Generator Management Relay 5-15 ACTUAL VALUES 5.1 OVERVIEW55 ACTUAL VALUES 5.1OVERVIEW 5.1.1 ACTUAL VALUES MESSAGESMeasured values, ma

Strany 40

5-2 489 Generator Management Relay GE Multilin5.1 OVERVIEW 5 ACTUAL VALUES5In addition to the actual value messages, there are also diagnostic and fla

Strany 41 - 32 I 151 A8 .000

GE Multilin 489 Generator Management Relay 5-35 ACTUAL VALUES 5.2 A1 STATUS55.2A1 STATUS 5.2.1 GENERATOR STATUSPATH: ACTUAL VALUES Ö A1 STATUS Ö GENER

Strany 42

5-4 489 Generator Management Relay GE Multilin5.2 A1 STATUS 5 ACTUAL VALUES5Immediately prior to issuing a trip, the 489 takes a snapshot of generator

Strany 43

GE Multilin 489 Generator Management Relay 5-55 ACTUAL VALUES 5.2 A1 STATUS5Input D ALARMSTATUS: ActiveRange: see Input A ALARM STATUSInput E ALARMSTA

Strany 44

5-6 489 Generator Management Relay GE Multilin5.2 A1 STATUS 5 ACTUAL VALUES5Any active or latched alarms may be viewed here.5.2.4 TRIP PICKUPSPATH: AC

Strany 45 - 808726A2.CDR

GE Multilin 489 Generator Management Relay 5-75 ACTUAL VALUES 5.2 A1 STATUS5Input CPICKUP: Not EnabledRange: see Input A PICKUP aboveInput DPICKUP: No

Strany 46 - 808730A2.CDR

1-6 489 Generator Management Relay GE Multilin1.2 SPECIFICATIONS 1 INTRODUCTION1Timing Accuracy: ±0.5 s or ±0.5% of total timeElements: Trip and Alarm

Strany 47 - CURRENT LEVEL

5-8 489 Generator Management Relay GE Multilin5.2 A1 STATUS 5 ACTUAL VALUES5NEUTRAL O/V (FUND)PICKUP: Not EnabledRange: Not Enabled, Inactive, Timing

Strany 48 - CLEAR EVENTS

GE Multilin 489 Generator Management Relay 5-95 ACTUAL VALUES 5.2 A1 STATUS5The trip pickup messages may be very useful during testing. They will indi

Strany 49

5-10 489 Generator Management Relay GE Multilin5.2 A1 STATUS 5 ACTUAL VALUES5UNDERVOLTAGEPICKUP: Not EnabledRange: Not Enabled, Inactive, Timing Out,

Strany 50

GE Multilin 489 Generator Management Relay 5-115 ACTUAL VALUES 5.2 A1 STATUS5The alarm pickup messages may be very useful during testing. They will in

Strany 51

5-12 489 Generator Management Relay GE Multilin5.2 A1 STATUS 5 ACTUAL VALUES55.2.6 DIGITAL INPUTSPATH: ACTUAL VALUES ÖØ A1 STATUS ÖØ DIGITAL INPUTSThe

Strany 52

GE Multilin 489 Generator Management Relay 5-135 ACTUAL VALUES 5.3 A2 METERING DATA55.3A2 METERING DATA 5.3.1 CURRENT METERINGPATH: ACTUAL VALUES ÖØ A

Strany 53

5-14 489 Generator Management Relay GE Multilin5.3 A2 METERING DATA 5 ACTUAL VALUES55.3.2 VOLTAGE METERINGPATH: ACTUAL VALUES ÖØ A2 METERING DATA ÖØ V

Strany 54

GE Multilin 489 Generator Management Relay 5-155 ACTUAL VALUES 5.3 A2 METERING DATA55.3.3 POWER METERINGPATH: ACTUAL VALUES ÖØ A2 METERING DATA ÖØ POW

Strany 55

5-16 489 Generator Management Relay GE Multilin5.3 A2 METERING DATA 5 ACTUAL VALUES55.3.4 TEMPERATUREPATH: ACTUAL VALUES ÖØ A2 METERING DATA ÖØ TEMPER

Strany 56 - ACTIVATE SET

GE Multilin 489 Generator Management Relay 5-175 ACTUAL VALUES 5.3 A2 METERING DATA55.3.5 DEMAND METERINGPATH: ACTUAL VALUES ÖØ A2 METERING DATA ÖØ DE

Strany 57

GE Multilin 489 Generator Management Relay 1-71 INTRODUCTION 1.2 SPECIFICATIONS1Elements: Trip and AlarmOVERFREQUENCYRequired Voltage: 0.50 to 0.99 ×

Strany 58

5-18 489 Generator Management Relay GE Multilin5.4 A3 LEARNED DATA 5 ACTUAL VALUES55.4A3 LEARNED DATA 5.4.1 PARAMETER AVERAGESPATH: ACTUAL VALUES ÖØ A

Strany 59

GE Multilin 489 Generator Management Relay 5-195 ACTUAL VALUES 5.4 A3 LEARNED DATA55.4.3 ANALOG INPUT MINIMUM/MAXIMUMPATH: ACTUAL VALUES ÖØ A3 LEARNED

Strany 60

5-20 489 Generator Management Relay GE Multilin5.5 A4 MAINTENANCE 5 ACTUAL VALUES55.5A4 MAINTENANCE 5.5.1 TRIP COUNTERSPATH: ACTUAL VALUES ÖØ A4 MAINT

Strany 61

GE Multilin 489 Generator Management Relay 5-215 ACTUAL VALUES 5.5 A4 MAINTENANCE5The number of trips by type is displayed here. When the total reache

Strany 62 - (EQ 4.1)

5-22 489 Generator Management Relay GE Multilin5.5 A4 MAINTENANCE 5 ACTUAL VALUES55.5.2 GENERAL COUNTERSPATH: ACTUAL VALUES ÖØ A4 MAINTENANCE ÖØ GENER

Strany 63 - (EQ 4.2)

GE Multilin 489 Generator Management Relay 5-235 ACTUAL VALUES 5.6 A5 EVENT RECORDER55.6A5 EVENT RECORDER 5.6.1 EVENT RECORDERPATH: ACTUAL VALUES ÖØ A

Strany 64 - Breaker Auxiliary b

5-24 489 Generator Management Relay GE Multilin5.6 A5 EVENT RECORDER 5 ACTUAL VALUES5The 489 Event Recorder stores generator and system information ea

Strany 65

GE Multilin 489 Generator Management Relay 5-255 ACTUAL VALUES 5.7 A6 PRODUCT INFO55.7A6 PRODUCT INFO 5.7.1 489 MODEL INFOPATH: ACTUAL VALUES ÖØ A6 PR

Strany 66

5-26 489 Generator Management Relay GE Multilin5.8 DIAGNOSTICS 5 ACTUAL VALUES55.8DIAGNOSTICS 5.8.1 DIAGNOSTIC MESSAGESIn the event of a trip or alarm

Strany 67

GE Multilin 489 Generator Management Relay 5-275 ACTUAL VALUES 5.8 DIAGNOSTICS55.8.2 FLASH MESSAGESFlash messages are warning, error, or general infor

Strany 68

1-8 489 Generator Management Relay GE Multilin1.2 SPECIFICATIONS 1 INTRODUCTION1At temperatures lower than –20°C, the LCD contrastmay be impaired.LONG

Strany 69

5-28 489 Generator Management Relay GE Multilin5.8 DIAGNOSTICS 5 ACTUAL VALUES5• SETPOINT ACCESS IS NOW RESTRICTED: If the passcode security feature i

Strany 70

GE Multilin 489 Generator Management Relay 5-295 ACTUAL VALUES 5.8 DIAGNOSTICS5• TOP OF LIST: This message will indicate when the top of subgroup has

Strany 71

5-30 489 Generator Management Relay GE Multilin5.8 DIAGNOSTICS 5 ACTUAL VALUES5

Strany 72

GE Multilin 489 Generator Management Relay 6-16 COMMUNICATIONS 6.1 MODBUS PROTOCOL66 COMMUNICATIONS 6.1MODBUS PROTOCOL 6.1.1 ELECTRICAL INTERFACEThe h

Strany 73

6-2 489 Generator Management Relay GE Multilin6.1 MODBUS PROTOCOL 6 COMMUNICATIONS6• DATA BYTES: This is a variable number of bytes depending on the F

Strany 74 - (EQ 4.8)

GE Multilin 489 Generator Management Relay 6-36 COMMUNICATIONS 6.2 MODBUS FUNCTIONS66.2MODBUS FUNCTIONS 6.2.1 SUPPORTED FUNCTIONSThe following functio

Strany 75 - 808731A1.CDR

6-4 489 Generator Management Relay GE Multilin6.2 MODBUS FUNCTIONS 6 COMMUNICATIONS66.2.3 FUNCTION CODE 05: EXECUTE OPERATIONModbus Implementation: Fo

Strany 76 - (EQ 4.9)

GE Multilin 489 Generator Management Relay 6-56 COMMUNICATIONS 6.2 MODBUS FUNCTIONS66.2.5 FUNCTION CODE 07: READ DEVICE STATUSModbus Implementation: R

Strany 77 - CURRENT VOLTAGE

6-6 489 Generator Management Relay GE Multilin6.2 MODBUS FUNCTIONS 6 COMMUNICATIONS66.2.7 FUNCTION CODE 16: STORE MULTIPLE SETPOINTSModbus Implementat

Strany 78 - (EQ 4.11)

GE Multilin 489 Generator Management Relay 6-76 COMMUNICATIONS 6.2 MODBUS FUNCTIONS66.2.8 FUNCTION CODE 16: PERFORMING COMMANDSSome PLCs may not suppo

Strany 79

GE Multilin 489 Generator Management Relay 2-12 INSTALLATION 2.1 MECHANICAL22 INSTALLATION 2.1MECHANICAL 2.1.1 DESCRIPTIONThe 489 is packaged in the s

Strany 80

6-8 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS66.3MODBUS MEMORY MAP 6.3.1 MEMORY MAP INFORMATIONThe data stored

Strany 81 - (multiples of CT)

GE Multilin 489 Generator Management Relay 6-96 COMMUNICATIONS 6.3 MODBUS MEMORY MAP66.3.4 WAVEFORM CAPTUREThe 489 stores up to 64 cycles of A/D sampl

Strany 82 - 808812A3.CDR

6-10 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS66.3.7 489 MEMORY MAPTable 6–1: 489 MEMORY MAP (SHEET 1 OF 24)ADD

Strany 83 - (EQ 4.18)

GE Multilin 489 Generator Management Relay 6-116 COMMUNICATIONS 6.3 MODBUS MEMORY MAP6025C HOTTEST STATOR RTD TEMPERATURE –50 to 250 1 °F F4 0025D HOT

Strany 84 - (EQ 4.19)

6-12 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS60306 INPUT G PICKUP 0 to 4 1 – F123 00307 TACHOMETER PICKUP 0 to

Strany 85 - TIME DELAY SETTING

GE Multilin 489 Generator Management Relay 6-136 COMMUNICATIONS 6.3 MODBUS MEMORY MAP60402 PHASE B OUTPUT CURRENT 0 to 999999 1 Amps F12 00404 PHASE C

Strany 86

6-14 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS604AC RTD #11 TEMPERATURE –52 to 251 1 °C F4 –5204AD RTD #12 TEMP

Strany 87

GE Multilin 489 Generator Management Relay 6-156 COMMUNICATIONS 6.3 MODBUS MEMORY MAP60706 ANALOG INPUT 2 MAXIMUM –50000 to 50000 1 Units F12 00708 AN

Strany 88

6-16 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS6489 SETUP / SERIAL PORTS1010 SLAVE ADDRESS 1 to 254 1 – F1 25410

Strany 89

GE Multilin 489 Generator Management Relay 6-176 COMMUNICATIONS 6.3 MODBUS MEMORY MAP61223 GENERAL INPUT A TRIP DELAY 1 to 50000 1 s F2 50DIGITAL INPU

Strany 90 - GROUNDINGSWITCH

2-2 489 Generator Management Relay GE Multilin2.1 MECHANICAL 2 INSTALLATION22.1.2 PRODUCT IDENTIFICATIONEach 489 unit and case are equipped with a per

Strany 91 - (EQ 4.22)

6-18 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS6DIGITAL INPUTS / GENERAL INPUT F12B0 ASSIGN DIGITAL INPUT 0 to 7

Strany 92 - (EQ 4.24)

GE Multilin 489 Generator Management Relay 6-196 COMMUNICATIONS 6.3 MODBUS MEMORY MAP6DIGITAL INPUTS / WAVEFORM CAPTURE13C0 ASSIGN DIGITAL INPUT 0 to

Strany 93

6-20 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS61624 FLEXCURVE TRIP TIME AT 4.00 × PU 0 to 65535 1 ms F1 6553516

Strany 94 - 808740A1.CDR

GE Multilin 489 Generator Management Relay 6-216 COMMUNICATIONS 6.3 MODBUS MEMORY MAP6CURRENT ELEMENTS / GROUND O/C1720 GROUND OVERCURRENT ALARM 0 to

Strany 95

6-22 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS61761 FLEXCURVE TRIP TIME AT 8.50 × PU 0 to 65535 1 ms F1 6553517

Strany 96 - (EQ 4.25)

GE Multilin 489 Generator Management Relay 6-236 COMMUNICATIONS 6.3 MODBUS MEMORY MAP62023 OVERVOLTAGE ALARM DELAY 1 to 1200 1 s F2 302024 OVERVOLTAGE

Strany 97

6-24 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS6VOLTAGE ELEMENTS / NEUTRAL U/V (3rd)20E0 LOW POWER BLOCKING LEVE

Strany 98

GE Multilin 489 Generator Management Relay 6-256 COMMUNICATIONS 6.3 MODBUS MEMORY MAP6POWER ELEMENTS / LOW FORWARD POWER2280 BLOCK LOW FWD POWER FROM

Strany 99

6-26 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS62525 RTD #5 TRIP 0 to 2 1 – F115 02526 RTD #5 TRIP VOTING 1 to 1

Strany 100

GE Multilin 489 Generator Management Relay 6-276 COMMUNICATIONS 6.3 MODBUS MEMORY MAP626A5 RTD #11 TRIP 0 to 2 1 – F115 026A6 RTD #11 TRIP VOTING 1 to

Strany 101

GE Multilin 489 Generator Management Relay 2-32 INSTALLATION 2.1 MECHANICAL22.1.3 INSTALLATIONThe 489 case, alone or adjacent to another SR unit, can

Strany 102

6-28 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS62846 TIME TO TRIP AT 20.0 × FLA 5 to 999999 1 s F10 52848 MINIMU

Strany 103

GE Multilin 489 Generator Management Relay 6-296 COMMUNICATIONS 6.3 MODBUS MEMORY MAP6MONITORING / RUNNING HOUR SETUP2AC0 INITIAL GEN. RUNNING HOUR 0

Strany 104

6-30 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS62B37 VOLTS/HERTZ MAX 0 to 200 1 × Rated F3 1502B38 FREQUENCY MIN

Strany 105 - 806827A1.CDR

GE Multilin 489 Generator Management Relay 6-316 COMMUNICATIONS 6.3 MODBUS MEMORY MAP62C58 ANALOG INPUT2 TRIP PICKUP 0 to 1 1 – F130 02C59 ANALOG INPU

Strany 106

6-32 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS62D83 FAULT Iphase NEUTRAL 0 to 2000 1 × CT F3 02D84 FAULT CURREN

Strany 107 - (EQ 4.27)

GE Multilin 489 Generator Management Relay 6-336 COMMUNICATIONS 6.3 MODBUS MEMORY MAP630E2 HOTTEST OTHER RTD TEMPERATURE –50 to 250 1 °F F4 030E3 HOTT

Strany 108 - TIME IN SECONDS

6-34 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS66.3.8 MEMORY MAP DATA FORMATSTable 6–2: DATA FORMATS (SHEET 1 OF

Strany 109 - (EQ 4.28)

GE Multilin 489 Generator Management Relay 6-356 COMMUNICATIONS 6.3 MODBUS MEMORY MAP6F107 Unsigned16 bit integerNominal frequency selection0 = -----,

Strany 110 - TIME TO TRIP IN SECONDS

6-36 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS6F131 Unsigned16 bit integerInput switch status0 = Closed, 1 = Op

Strany 111 - FOR HIGH INERTIAL LOAD

GE Multilin 489 Generator Management Relay 6-376 COMMUNICATIONS 6.3 MODBUS MEMORY MAP6F139 Unsigned16 bit integerForce operation of relaysF140 16 bits

Strany 113 - OVERLOAD PROTECTION CURVES

2-4 489 Generator Management Relay GE Multilin2.1 MECHANICAL 2 INSTALLATION23. Grasp the locking handle in the center and pull firmly, rotating the ha

Strany 114 - OVERLOAD PROTECTION at 80% V

6-38 489 Generator Management Relay GE Multilin6.3 MODBUS MEMORY MAP 6 COMMUNICATIONS6F211 Unsigned16 bit integerVolts/Hertz element type0 = Curve #1,

Strany 115 - NEMA GE MULTILIN

GE Multilin 489 Generator Management Relay 6-396 COMMUNICATIONS 6.4 DNP PROTOCOL66.4DNP PROTOCOL 6.4.1 DEVICE PROFILE DOCUMENTDNP 3.0DEVICE PROFILE DO

Strany 116 - 80% LOAD

6-40 489 Generator Management Relay GE Multilin6.4 DNP PROTOCOL 6 COMMUNICATIONS6Reports Binary Input Change Events when no specific variations reques

Strany 117

GE Multilin 489 Generator Management Relay 6-416 COMMUNICATIONS 6.4 DNP PROTOCOL66.4.2 IMPLEMENTATION TABLEThe table below gives a list of all objects

Strany 118 - 808721A1.CDR

6-42 489 Generator Management Relay GE Multilin6.4 DNP PROTOCOL 6 COMMUNICATIONS6IMPLEMENTATION TABLE NOTES:1. For this object, the quantity specified

Strany 119

GE Multilin 489 Generator Management Relay 6-436 COMMUNICATIONS 6.5 DNP POINT LISTS66.5DNP POINT LISTS 6.5.1 BINARY INPUT / BINARY INPUT CHANGE (OBJEC

Strany 120 - Range: On, Off

6-44 489 Generator Management Relay GE Multilin6.5 DNP POINT LISTS 6 COMMUNICATIONS6Any detected change in the state of any point assigned to Class 1

Strany 121

GE Multilin 489 Generator Management Relay 6-456 COMMUNICATIONS 6.5 DNP POINT LISTS66.5.2 BINARY / CONTROL RELAY OUTPUT BLOCK (OBJECTS 10/12)The follo

Strany 122

6-46 489 Generator Management Relay GE Multilin6.5 DNP POINT LISTS 6 COMMUNICATIONS66.5.3 BINARY / FROZEN COUNTER (OBJECTS 20/21)The counters cannot b

Strany 123 - (EQ 4.38)

GE Multilin 489 Generator Management Relay 6-476 COMMUNICATIONS 6.5 DNP POINT LISTS66.5.4 ANALOG INPUT / INPUT CHANGE (OBJECTS 30/32)In the following

Strany 124 - 808738A1.CDR

GE Multilin 489 Generator Management Relay 2-52 INSTALLATION 2.1 MECHANICAL22.1.5 TERMINAL LOCATIONSFigure 2–8: TERMINAL LAYOUT

Strany 125

6-48 489 Generator Management Relay GE Multilin6.5 DNP POINT LISTS 6 COMMUNICATIONS638 F12 Pre-Trip Analog Input 2 Class 1 Notes 3,939 F12 Pre-Trip A

Strany 126

GE Multilin 489 Generator Management Relay 6-496 COMMUNICATIONS 6.5 DNP POINT LISTS683 F1 Reactive Power (Mar) Class 2 Note 884 F1 Reactive Power (kva

Strany 127

6-50 489 Generator Management Relay GE Multilin6.5 DNP POINT LISTS 6 COMMUNICATIONS6TABLE NOTES:1. Unless otherwise specified, an event object will be

Strany 128

GE Multilin 489 Generator Management Relay 7-17 TESTING 7.1 TEST SETUP77 TESTING 7.1TEST SETUP 7.1.1 DESCRIPTIONThe purpose of this testing descriptio

Strany 129

7-2 489 Generator Management Relay GE Multilin7.1 TEST SETUP 7 TESTING77.1.2 SECONDARY CURRENT INJECTION TEST SETUPFigure 7–1: SECONDARY CURRENT INJEC

Strany 130

GE Multilin 489 Generator Management Relay 7-37 TESTING 7.2 HARDWARE FUNCTIONAL TESTS77.2HARDWARE FUNCTIONAL TESTS 7.2.1 OUTPUT CURRENT ACCURACYThe sp

Strany 131

7-4 489 Generator Management Relay GE Multilin7.2 HARDWARE FUNCTIONAL TESTS 7 TESTING77.2.3 GROUND (1 A), NEUTRAL, AND DIFFERENTIAL CURRENT ACCURACYTh

Strany 132

GE Multilin 489 Generator Management Relay 7-57 TESTING 7.2 HARDWARE FUNCTIONAL TESTS77.2.5 NEGATIVE SEQUENCE CURRENT ACCURACYThe 489 measures negativ

Strany 133

7-6 489 Generator Management Relay GE Multilin7.2 HARDWARE FUNCTIONAL TESTS 7 TESTING77.2.6 RTD ACCURACYThe specification for RTD input accuracy is ±2

Strany 134

GE Multilin 489 Generator Management Relay 7-77 TESTING 7.2 HARDWARE FUNCTIONAL TESTS77.2.7 DIGITAL INPUTS AND TRIP COIL SUPERVISIONThe digital inputs

Strany 135

2-6 489 Generator Management Relay GE Multilin2.1 MECHANICAL 2 INSTALLATION2Table 2–1: 489 TERMINAL LISTTERMINAL DESCRIPTION TERMINAL DESCRIPTIONA01 R

Strany 136

7-8 489 Generator Management Relay GE Multilin7.2 HARDWARE FUNCTIONAL TESTS 7 TESTING70 to 1 mA ANALOG INPUTS:1. Alter the following setpoints:S11 ANA

Strany 137

GE Multilin 489 Generator Management Relay 7-97 TESTING 7.3 ADDITIONAL FUNCTIONAL TESTS77.3ADDITIONAL FUNCTIONAL TESTS 7.3.1 OVERLOAD CURVE ACCURACYTh

Strany 138

7-10 489 Generator Management Relay GE Multilin7.3 ADDITIONAL FUNCTIONAL TESTS 7 TESTING77.3.2 POWER MEASUREMENT TESTThe specification for reactive an

Strany 139

GE Multilin 489 Generator Management Relay 7-117 TESTING 7.3 ADDITIONAL FUNCTIONAL TESTS77.3.3 REACTIVE POWER ACCURACYThe specification for reactive p

Strany 140

7-12 489 Generator Management Relay GE Multilin7.3 ADDITIONAL FUNCTIONAL TESTS 7 TESTING77.3.4 VOLTAGE PHASE REVERSAL ACCURACYThe can detect voltage p

Strany 141

GE Multilin 489 Generator Management Relay 7-137 TESTING 7.3 ADDITIONAL FUNCTIONAL TESTS77.3.6 GE MULTILIN HGF GROUND ACCURACYThe specification for GE

Strany 142

7-14 489 Generator Management Relay GE Multilin7.3 ADDITIONAL FUNCTIONAL TESTS 7 TESTING77.3.8 PHASE DIFFERENTIAL TRIP ACCURACYThese tests will requir

Strany 143

GE Multilin 489 Generator Management Relay 7-157 TESTING 7.3 ADDITIONAL FUNCTIONAL TESTS7f) TEST RESULTS7.3.9 INJECTION TEST SETUP #3Setup the 489 dev

Strany 144

7-16 489 Generator Management Relay GE Multilin7.3 ADDITIONAL FUNCTIONAL TESTS 7 TESTING77.3.10 VOLTAGE RESTRAINED OVERCURRENT ACCURACYSetup the relay

Strany 145

GE Multilin 489 Generator Management Relay A-1APPENDIX A A.1 STATOR GROUND FAULTAAPPENDIX A Application NotesA.1 Stator Ground Fault A.1.1 DESCRIPTIO

Strany 146

GE Multilin 489 Generator Management Relay 2-72 INSTALLATION 2.2 ELECTRICAL22.2ELECTRICAL 2.2.1 TYPICAL WIRING DIAGRAMFigure 2–9: TYPICAL WIRING DIAGR

Strany 147

A-2 489 Generator Management Relay GE MultilinA.1 STATOR GROUND FAULT APPENDIX A AWhen several small generators are operated in parallel with a single

Strany 148

GE Multilin 489 Generator Management Relay A-3APPENDIX A A.1 STATOR GROUND FAULTAAgain the time delay on this element must be coordinated with protec

Strany 149 - TURE NOT PROGRAMMED

A-4 489 Generator Management Relay GE MultilinA.1 STATOR GROUND FAULT APPENDIX A AFigure A–5: GROUND DIRECTIONAL ELEMENT CONCEPTUAL ARRANGEMENTThe ope

Strany 150 - THIS FEATURE NOT PRO

GE Multilin 489 Generator Management Relay A-5APPENDIX A A.1 STATOR GROUND FAULTAA.1.5 THIRD HARMONIC VOLTAGE ELEMENTThe conventional neutral overvol

Strany 151

A-6 489 Generator Management Relay GE MultilinA.2 CURRENT TRANSFORMERS APPENDIX A AA.2 Current Transformers A.2.1 GROUND FAULT CTS FOR 50:0.025 A CTCT

Strany 152

GE Multilin 489 Generator Management Relay A-7APPENDIX A A.2 CURRENT TRANSFORMERSAA.2.2 GROUND FAULT CTS FOR 5 A SECONDARY CTFor low resistance or so

Strany 153

A-8 489 Generator Management Relay GE MultilinA.2 CURRENT TRANSFORMERS APPENDIX A AA.2.3 PHASE CTSCurrent transformers in most common ratios from 50:5

Strany 154

GE Multilin 489 Generator Management Relay B-1APPENDIX B B.1 TIME OVERCURRENT CURVESBAPPENDIX B CurvesB.1 Time Overcurrent Curves B.1.1 ANSI CURVESFi

Strany 155

B-2 489 Generator Management Relay GE MultilinB.1 TIME OVERCURRENT CURVES APPENDIX B BFigure B–2: ANSI NORMALLY INVERSE CURVES0.010.111010010000.11101

Strany 156

GE Multilin 489 Generator Management Relay B-3APPENDIX B B.1 TIME OVERCURRENT CURVESBFigure B–3: ANSI VERY INVERSE CURVES0.01808800A4.DWG0.1110100100

Strany 157

2-8 489 Generator Management Relay GE Multilin2.2 ELECTRICAL 2 INSTALLATION22.2.2 GENERAL WIRING CONSIDERATIONSA broad range of applications are avail

Strany 158 - LOCKOUTS:

B-4 489 Generator Management Relay GE MultilinB.1 TIME OVERCURRENT CURVES APPENDIX B BFigure B–4: ANSI EXTREMELY INVERSE CURVES0.01808799A4.CDR0.11101

Strany 159

GE Multilin 489 Generator Management Relay B-5APPENDIX B B.1 TIME OVERCURRENT CURVESBB.1.2 DEFINITE TIME CURVESFigure B–5: DEFINITE TIME CURVES489DEF

Strany 160

B-6 489 Generator Management Relay GE MultilinB.1 TIME OVERCURRENT CURVES APPENDIX B BB.1.3 IAC CURVESFigure B–6: IAC SHORT INVERSE CURVES0.51.02.03.0

Strany 161

GE Multilin 489 Generator Management Relay B-7APPENDIX B B.1 TIME OVERCURRENT CURVESBFigure B–7: IAC INVERSE CURVES0.51.02.03.04.06.08.010.015.020.03

Strany 162

B-8 489 Generator Management Relay GE MultilinB.1 TIME OVERCURRENT CURVES APPENDIX B BFigure B–8: IAC VERY INVERSE CURVES0.51.02.03.04.06.08.010.015.0

Strany 163

GE Multilin 489 Generator Management Relay B-9APPENDIX B B.1 TIME OVERCURRENT CURVESBFigure B–9: IAC EXTREME INVERSE CURVES0.51.02.03.04.06.08.010.01

Strany 164

B-10 489 Generator Management Relay GE MultilinB.1 TIME OVERCURRENT CURVES APPENDIX B BB.1.4 IEC CURVESFigure B–10: IEC CURVES A (BS142)0.050.100.150.

Strany 165

GE Multilin 489 Generator Management Relay B-11APPENDIX B B.1 TIME OVERCURRENT CURVESBFigure B–11: IEC CURVES B (BS142)0.050.100.150.200.300.400.500.

Strany 166

B-12 489 Generator Management Relay GE MultilinB.1 TIME OVERCURRENT CURVES APPENDIX B BFigure B–12: IEC CURVES C (BS142)0.050.100.150.200.300.400.500.

Strany 167

GE Multilin 489 Generator Management Relay C-1APPENDIX C C.1 REVISION HISTORYCAPPENDIX C MiscellaneousC.1 Revision History C.1.1 CHANGE NOTESC.1.2 CH

Strany 168

GE Multilin 489 Generator Management Relay 2-92 INSTALLATION 2.2 ELECTRICAL22.2.3 CONTROL POWERControl power supplied to the 489 must match the instal

Strany 169

C-2 489 Generator Management Relay GE MultilinC.2 EU DECLARATION OF CONFORMITY APPENDIX C CC.2 EU Declaration of Conformity C.2.1 EU DECLARATION OF C

Strany 170

GE Multilin 489 Generator Management Relay C-3APPENDIX C C.3 WARRANTY INFORMATIONCC.3 Warranty Information C.3.1 GE MULTILIN WARRANTYGE Multilin Rela

Strany 171

C-4 489 Generator Management Relay GE MultilinC.3 WARRANTY INFORMATION APPENDIX C C

Strany 172 - 6.3.7 489 MEMORY MAP

GE Multilin 489 Generator Management Relay 1INDEXNumerics0-1mA ANALOG INPUT ... 2-124-20mA ANALOG INP

Strany 173

2 489 Generator Management Relay GE MultilinINDEXEELECTRICAL INTERFACE ...6-1EMERGENCY RESTARTS ...

Strany 174

GE Multilin 489 Generator Management Relay 3INDEXNNEGATIVE SEQUENCE CURRENT ACCURACY TEST ... 7-5NEGATIVE SEQUENCE OVERCURRENT ...

Strany 175

4 489 Generator Management Relay GE MultilinINDEXconfiguration ...3-7installation ..

Strany 176

FIGURE 1–1: SINGLE LINE DIAGRAM ...

Strany 177

FIGURE B–8: IAC VERY INVERSE CURVES ...

Strany 178

TABLE: 1–1 TRIP AND ALARM PROTECTION FEATURES ...

Strany 179

2-10 489 Generator Management Relay GE Multilin2.2 ELECTRICAL 2 INSTALLATION2b) GROUND CURRENTDO NOT INJECT OVER THE RATED CURRENT TO HGF TERMINAL (0.

Strany 180

GE Multilin 489 Generator Management Relay 2-112 INSTALLATION 2.2 ELECTRICAL22.2.5 VOLTAGE INPUTSThe 489 has four voltage transformer inputs, three fo

Strany 181

2-12 489 Generator Management Relay GE Multilin2.2 ELECTRICAL 2 INSTALLATION22.2.8 ANALOG OUTPUTSThe 489 provides four analog output channels, which w

Strany 182

GE Multilin 489 Generator Management Relay 2-132 INSTALLATION 2.2 ELECTRICAL22.2.10 OUTPUT RELAYSThere are six Form C output relays (see the SPECIFICA

Strany 183

GE Multilin 489 Generator Management Relay 1 TABLE OF CONTENTS 1. INTRODUCTION 1.1 OVERVIEW1.1.1 Description ...

Strany 184

2-14 489 Generator Management Relay GE Multilin2.2 ELECTRICAL 2 INSTALLATION22.2.12 RS485 COMMUNICATIONS PORTSTwo independent two-wire RS485 ports are

Strany 185

GE Multilin 489 Generator Management Relay 2-152 INSTALLATION 2.2 ELECTRICAL22.2.13 DIELECTRIC STRENGTHIt may be required to test a complete motor sta

Strany 186

2-16 489 Generator Management Relay GE Multilin2.2 ELECTRICAL 2 INSTALLATION2

Strany 187

GE Multilin 489 Generator Management Relay 3-13 USER INTERFACES 3.1 FACEPLATE INTERFACE33 USER INTERFACES 3.1FACEPLATE INTERFACE 3.1.1 DISPLAYAll mess

Strany 188

3-2 489 Generator Management Relay GE Multilin3.1 FACEPLATE INTERFACE 3 USER INTERFACES3• VT FAILURE: Indicates that the VT fuse failure alarm is pick

Strany 189

GE Multilin 489 Generator Management Relay 3-33 USER INTERFACES 3.1 FACEPLATE INTERFACE32. Press the or key until "G" appears, then pres

Strany 190

3-4 489 Generator Management Relay GE Multilin3.2 SOFTWARE INTERFACE 3 USER INTERFACES33.2SOFTWARE INTERFACE 3.2.1 REQUIREMENTSThe 489PC software is n

Strany 191

GE Multilin 489 Generator Management Relay 3-53 USER INTERFACES 3.2 SOFTWARE INTERFACE33.2.2 INSTALLATION/UPGRADEa) CHECKING IF INSTALLATION/UPGRADE I

Strany 192

3-6 489 Generator Management Relay GE Multilin3.2 SOFTWARE INTERFACE 3 USER INTERFACES3b) INSTALLING/UPGRADING 489PCInstallation/upgrade of the 489PC

Strany 193

GE Multilin 489 Generator Management Relay 3-73 USER INTERFACES 3.2 SOFTWARE INTERFACE33.2.3 CONFIGURATION1. Connect the computer running 489PC to the

Strany 194

2 489 Generator Management Relay GE Multilin TABLE OF CONTENTS 4.2.6 Message Scratchpad ...

Strany 195

3-8 489 Generator Management Relay GE Multilin3.2 SOFTWARE INTERFACE 3 USER INTERFACES33.2.4 USING 489PCa) SAVING SETPOINTS TO A FILESetpoints must be

Strany 196 - 6.3.8 MEMORY MAP DATA FORMATS

GE Multilin 489 Generator Management Relay 3-93 USER INTERFACES 3.2 SOFTWARE INTERFACE35. The 489PC software automatically lists all filenames beginni

Strany 197

3-10 489 Generator Management Relay GE Multilin3.2 SOFTWARE INTERFACE 3 USER INTERFACES3d) ENTERING SETPOINTSThe following example illustrates how set

Strany 198

GE Multilin 489 Generator Management Relay 3-113 USER INTERFACES 3.2 SOFTWARE INTERFACE33. Select the File > Open menu item and enter the location

Strany 199

3-12 489 Generator Management Relay GE Multilin3.2 SOFTWARE INTERFACE 3 USER INTERFACES33.2.5 TRENDINGTrending from the 489 can be accomplished via th

Strany 200

GE Multilin 489 Generator Management Relay 3-133 USER INTERFACES 3.2 SOFTWARE INTERFACE35. Select the Sample Rate through the pull-down menu, click th

Strany 201

3-14 489 Generator Management Relay GE Multilin3.2 SOFTWARE INTERFACE 3 USER INTERFACES33.2.6 WAVEFORM CAPTUREThe 489PC software can be used to captur

Strany 202 -  Configurable

GE Multilin 489 Generator Management Relay 3-153 USER INTERFACES 3.2 SOFTWARE INTERFACE33.2.7 PHASORSThe 489PC software can be used to view the phasor

Strany 203

3-16 489 Generator Management Relay GE Multilin3.2 SOFTWARE INTERFACE 3 USER INTERFACES33.2.8 EVENT RECORDERThe 489 event recorder can be viewed throu

Strany 204

GE Multilin 489 Generator Management Relay 3-173 USER INTERFACES 3.2 SOFTWARE INTERFACE33.2.9 TROUBLESHOOTINGThis section provides some procedures for

Strany 205

GE Multilin 489 Generator Management Relay 3 TABLE OF CONTENTS 4.11 S10 MONITORING4.11.1 Trip Counter ...

Strany 206

3-18 489 Generator Management Relay GE Multilin3.2 SOFTWARE INTERFACE 3 USER INTERFACES3

Strany 207

GE Multilin 489 Generator Management Relay 4-14 SETPOINTS 4.1 OVERVIEW44 SETPOINTS 4.1OVERVIEW 4.1.1 SETPOINT MESSAGE MAP S1 SETPOINTS 489 SETUP

Strany 208

4-2 489 Generator Management Relay GE Multilin4.1 OVERVIEW 4 SETPOINTS4 FIELD-BKR DISCREP. [ENTER] for moreSee page 4–18. TACHOMETER [ENTER] for m

Strany 209

GE Multilin 489 Generator Management Relay 4-34 SETPOINTS 4.1 OVERVIEW4 OVERFREQUENCY [ENTER] for moreSee page 4–38. NEUTRAL OV (Fund) [ENTER] for

Strany 210

4-4 489 Generator Management Relay GE Multilin4.1 OVERVIEW 4 SETPOINTS4 VT FUSE FAILURE [ENTER] for moreSee page 4–71. CURRENT DEMAND [ENTER] for

Strany 211

GE Multilin 489 Generator Management Relay 4-54 SETPOINTS 4.1 OVERVIEW44.1.2 TRIPS / ALARMS/ CONTROL FEATURESThe 489 Generator Management Relay has th

Strany 212

4-6 489 Generator Management Relay GE Multilin4.1 OVERVIEW 4 SETPOINTS44.1.4 DUAL SETPOINTSThe 489 has dual settings for the current, voltage, power,

Strany 213

GE Multilin 489 Generator Management Relay 4-74 SETPOINTS 4.2 S1 489 SETUP44.2S1 489 SETUP 4.2.1 PASSCODEPATH: SETPOINTS Ö S1 489 SETUP Ö PASSCODEA pa

Strany 214 - 7.1 TEST SETUP 7 TESTING

4-8 489 Generator Management Relay GE Multilin4.2 S1 489 SETUP 4 SETPOINTS4Some of the 489 characteristics can be modified to suit different situation

Strany 215

GE Multilin 489 Generator Management Relay 4-94 SETPOINTS 4.2 S1 489 SETUP44.2.4 REAL TIME CLOCKPATH: SETPOINTS Ö S1 489 SETUP ÖØ REAL TIME CLOCKFor e

Strany 216

4 489 Generator Management Relay GE Multilin TABLE OF CONTENTS 6.1.2 Modbus RTU Description...

Strany 217

4-10 489 Generator Management Relay GE Multilin4.2 S1 489 SETUP 4 SETPOINTS4The 489 displays default messages after a period of keypad inactivity. Up

Strany 218 - TEMPERATURE

GE Multilin 489 Generator Management Relay 4-114 SETPOINTS 4.2 S1 489 SETUP44.2.7 CLEAR DATAPATH: SETPOINTS Ö S1 489 SETUP ÖØ CLEAR DATAThese commands

Strany 219

4-12 489 Generator Management Relay GE Multilin4.3 S2 SYSTEM SETUP 4 SETPOINTS44.3S2 SYSTEM SETUP 4.3.1 CURRENT SENSINGPATH: SETPOINTS ÖØ S2 SYSTEM SE

Strany 220

GE Multilin 489 Generator Management Relay 4-134 SETPOINTS 4.3 S2 SYSTEM SETUP44.3.3 GENERATOR PARAMETERSPATH: SETPOINTS ÖØ S2 SYSTEM SETUP ÖØ GENERAT

Strany 221

4-14 489 Generator Management Relay GE Multilin4.4 S3 DIGITAL INPUTS 4 SETPOINTS44.4S3 DIGITAL INPUTS 4.4.1 DESCRIPTIONThe 489 has nine (9) digital in

Strany 222

GE Multilin 489 Generator Management Relay 4-154 SETPOINTS 4.4 S3 DIGITAL INPUTS44.4.3 GENERAL INPUT A TO GPATH: SETPOINTS ÖØ S3 DIGITAL INPUTS ÖØ GEN

Strany 223

4-16 489 Generator Management Relay GE Multilin4.4 S3 DIGITAL INPUTS 4 SETPOINTS44.4.4 REMOTE RESETPATH: SETPOINTS ÖØ S3 DIGITAL INPUTS ÖØ REMOTE RESE

Strany 224 - 3 PHASE VARIABLE AC TEST SET

GE Multilin 489 Generator Management Relay 4-174 SETPOINTS 4.4 S3 DIGITAL INPUTS4The following chart illustrates the Group 2 (alternate group) setpoin

Strany 225

4-18 489 Generator Management Relay GE Multilin4.4 S3 DIGITAL INPUTS 4 SETPOINTS44.4.9 FIELD-BREAKER DISCREPANCYPATH: SETPOINTS ÖØ S3 DIGITAL INPUTS Ö

Strany 226 - (EQ 7.7)

GE Multilin 489 Generator Management Relay 4-194 SETPOINTS 4.4 S3 DIGITAL INPUTS4One of assignable digital inputs 4 to 7 may be assigned to the tachom

Strany 227

GE Multilin 489 Generator Management Relay 5 TABLE OF CONTENTS A. APPLICATION NOTES A.1 STATOR GROUND FAULTA.1.1 Description ...

Strany 228

4-20 489 Generator Management Relay GE Multilin4.5 S4 OUTPUT RELAYS 4 SETPOINTS44.5S4 OUTPUT RELAYS 4.5.1 DESCRIPTIONFive of the six output relays are

Strany 229 - 808739A1.CDR

GE Multilin 489 Generator Management Relay 4-214 SETPOINTS 4.6 S5 CURRENT ELEMENTS44.6S5 CURRENT ELEMENTS 4.6.1 INVERSE TIME OVERCURRENT CURVE CHARACT

Strany 230

4-22 489 Generator Management Relay GE Multilin4.6 S5 CURRENT ELEMENTS 4 SETPOINTS4c) IEC CURVESFor European applications, the relay offers the four s

Strany 231 - 808735A1.CDR

GE Multilin 489 Generator Management Relay 4-234 SETPOINTS 4.6 S5 CURRENT ELEMENTS4e) FLEXCURVE™The custom FlexCurve™ has setpoints for entering times

Strany 232 - 808734A1.CDR

4-24 489 Generator Management Relay GE Multilin4.6 S5 CURRENT ELEMENTS 4 SETPOINTS44.6.2 OVERCURRENT ALARMPATH: SETPOINTS ÖØ S5 CURRENT ELEMENTS Ö OVE

Strany 233 - (EQ A.2)

GE Multilin 489 Generator Management Relay 4-254 SETPOINTS 4.6 S5 CURRENT ELEMENTS44.6.4 INADVERTENT ENERGIZATIONPATH: SETPOINTS ÖØ S5 CURRENT ELEMENT

Strany 234 - DIMENSIONS

4-26 489 Generator Management Relay GE Multilin4.6 S5 CURRENT ELEMENTS 4 SETPOINTS44.6.5 VOLTAGE RESTRAINED PHASE OVERCURRENTPATH: SETPOINTS ÖØ S5 CUR

Strany 235

GE Multilin 489 Generator Management Relay 4-274 SETPOINTS 4.6 S5 CURRENT ELEMENTS4The 489 phase overcurrent restraint voltages and restraint characte

Strany 236 - 808712A1.CDR

4-28 489 Generator Management Relay GE Multilin4.6 S5 CURRENT ELEMENTS 4 SETPOINTS4 defines the short time negative sequence capability of the generat

Strany 237 - MODERATELY INVERSE

GE Multilin 489 Generator Management Relay 4-294 SETPOINTS 4.6 S5 CURRENT ELEMENTS44.6.7 GROUND OVERCURRENTPATH: SETPOINTS ÖØ S5 CURRENT ELEMENTS ÖØ G

Strany 238 - NORMALLY INVERSE

6 489 Generator Management Relay GE Multilin TABLE OF CONTENTS

Strany 239 - VERY INVERSE

4-30 489 Generator Management Relay GE Multilin4.6 S5 CURRENT ELEMENTS 4 SETPOINTS44.6.8 PHASE DIFFERENTIALPATH: SETPOINTS ÖØ S5 CURRENT ELEMENTS ÖØ P

Strany 240 - TRIPTIME (sec)

GE Multilin 489 Generator Management Relay 4-314 SETPOINTS 4.6 S5 CURRENT ELEMENTS4Figure 4–4: DIFFERENTIAL ELEMENTS4.6.9 GROUND DIRECTIONALPATH: SETP

Strany 241 - DEFINITE TIME

4-32 489 Generator Management Relay GE Multilin4.6 S5 CURRENT ELEMENTS 4 SETPOINTS4The 489 detects ground directional by using two measurement quantit

Strany 242 - SHORT INVERSE

GE Multilin 489 Generator Management Relay 4-334 SETPOINTS 4.7 S6 VOLTAGE ELEMENTS44.7S6 VOLTAGE ELEMENTS 4.7.1 UNDERVOLTAGEPATH: SETPOINTS ÖØ S6 VOLT

Strany 243 - IAC INVERSE

4-34 489 Generator Management Relay GE Multilin4.7 S6 VOLTAGE ELEMENTS 4 SETPOINTS44.7.2 OVERVOLTAGEPATH: SETPOINTS ÖØ S6 VOLTAGE ELEMENTS ÖØ OVERVOLT

Strany 244

GE Multilin 489 Generator Management Relay 4-354 SETPOINTS 4.7 S6 VOLTAGE ELEMENTS44.7.3 VOLTS/HERTZPATH: SETPOINTS ÖØ S6 VOLTAGE ELEMENTS ÖØ VOLTS/HE

Strany 245 - EXTREME INVERSE

4-36 489 Generator Management Relay GE Multilin4.7 S6 VOLTAGE ELEMENTS 4 SETPOINTS4Volts/Hertz is calculated per unit as follows: 4.7.4 PHASE REVERSAL

Strany 246 - IEC CURVE A (BS142)

GE Multilin 489 Generator Management Relay 4-374 SETPOINTS 4.7 S6 VOLTAGE ELEMENTS44.7.5 UNDERFREQUENCYPATH: SETPOINTS ÖØ S6 VOLTAGE ELEMENTS ÖØ UNDER

Strany 247 - IEC CURVE B (BS142)

4-38 489 Generator Management Relay GE Multilin4.7 S6 VOLTAGE ELEMENTS 4 SETPOINTS44.7.6 OVERFREQUENCYPATH: SETPOINTS ÖØ S6 VOLTAGE ELEMENTS ÖØ OVERFR

Strany 248 - IEC CURVE C (BS142)

GE Multilin 489 Generator Management Relay 4-394 SETPOINTS 4.7 S6 VOLTAGE ELEMENTS44.7.7 NEUTRAL OVERVOLTAGE (FUNDAMENTAL)PATH: SETPOINTS ÖØ S6 VOLTAG

Strany 249

GE Multilin 489 Generator Management Relay 1-11 INTRODUCTION 1.1 OVERVIEW11 INTRODUCTION 1.1OVERVIEW 1.1.1 DESCRIPTIONThe 489 Generator Management Rel

Strany 250

4-40 489 Generator Management Relay GE Multilin4.7 S6 VOLTAGE ELEMENTS 4 SETPOINTS4Figure 4–6: NEUTRAL OVERVOLTAGE DETECTIONIf the ground directional

Strany 251 - GE Multilin Relay Warranty

GE Multilin 489 Generator Management Relay 4-414 SETPOINTS 4.7 S6 VOLTAGE ELEMENTS4The neutral undervoltage function responds to 3rd harmonic voltage

Strany 252

4-42 489 Generator Management Relay GE Multilin4.7 S6 VOLTAGE ELEMENTS 4 SETPOINTS44.7.9 LOSS OF EXCITATIONPATH: SETPOINTS ÖØ S6 VOLTAGE ELEMENTS ÖØ L

Strany 253 - Numerics

GE Multilin 489 Generator Management Relay 4-434 SETPOINTS 4.7 S6 VOLTAGE ELEMENTS4where: Zprimary= primary ohms impedanceCT Ratio = programmed CT rat

Strany 254

4-44 489 Generator Management Relay GE Multilin4.7 S6 VOLTAGE ELEMENTS 4 SETPOINTS4The distance protection function (ANSI device 21) implements two zo

Strany 255

GE Multilin 489 Generator Management Relay 4-454 SETPOINTS 4.8 S7 POWER ELEMENTS44.8S7 POWER ELEMENTS 4.8.1 POWER MEASUREMENT CONVENTIONSGeneration of

Strany 256

4-46 489 Generator Management Relay GE Multilin4.8 S7 POWER ELEMENTS 4 SETPOINTS44.8.2 REACTIVE POWERPATH: SETPOINTS ÖØ S7 POWER ELEMENTS Ö REACTIVE P

Strany 257

GE Multilin 489 Generator Management Relay 4-474 SETPOINTS 4.8 S7 POWER ELEMENTS44.8.3 REVERSE POWERPATH: SETPOINTS ÖØ S7 POWER ELEMENTS ÖØ REVERSE PO

Strany 258

4-48 489 Generator Management Relay GE Multilin4.8 S7 POWER ELEMENTS 4 SETPOINTS44.8.4 LOW FORWARD POWERPATH: SETPOINTS ÖØ S7 POWER ELEMENTS ÖØ LOW FO

Strany 259

GE Multilin 489 Generator Management Relay 4-494 SETPOINTS 4.9 S8 RTD TEMPERATURE44.9S8 RTD TEMPERATURE 4.9.1 RTD TYPESPATH: SETPOINTS ÖØ S8 RTD TEMPE